TX7008R Intelligent Fire Alarm Control Panel

Features and Advantages
  • Compliant with EN54-2 and EN54-4 standards
  • Advanced microprocessor technology with large memory capacity
  • Enhanced user interface combining touch LCD display and keypad
  • Real-time visual algorithm support
  • Improved false alarm protection
  • Programming via keypad and PC
  • Support for multiple interface protocols: USB / Ethernet / CAN Bus / RS485 serial port / Fiber optic
  • Support for loop-powered devices to further reduce cabling costs
  • Built-in printer and 160 zone LED indicators
  • Easy commissioning
  • Automatic device registration
  • Loop mapping with color-coded status
  • Device mismatch and dual-address conflict monitoring
  • Command builder for configuring fire response logic scenarios
  • Loop surge protection
  • Single-operator sounder on/off test capability
  • Programming access lock
System Capacity
  • Up to 254 devices per loop (up to 2032 under optimal conditions)
  • Network: up to 512 nodes
  • Zones: up to 3000
  • Groups: up to 3000
Technical Specifications
  • Input voltage: 230 VAC +10% / –15%, 50 Hz
  • Panel-to-panel networking: 512 panels connected in a single ring (under optimal conditions)
  • Communication board: CAN Bus
  • Protocol / Addressing: T&A, address range 1–254
  • Number of loops: 10 loops (standalone)
  • Protection: Built-in 4 kV surge protection
Panel Inputs / Outputs
  • Programmable relays: 4 circuits, normally open / normally closed contacts
  • Programmable input: 1 circuit, 24 VDC limited power
  • Programmable auxiliary power supply: 19–28 VDC limited voltage
  • Fixed outputs: 2 circuits, 18–28 VDC limited power
  • Indicators: 24 status LEDs / 160 zone LEDs
  • Display: 7-inch TFT touch screen
  • Keypad: 5 emergency response buttons and programming keypad
  • Material / Color: Sheet metal enclosure / black
  • Dimensions (H × W × D): 1715 × 550 × 480 mm
  • Operating temperature: –5°C to +40°C
  • Humidity: 0–95% relative humidity, non-condensing